Type of power station | Space Type | Area | Operator Usage | Device Type | Number of cabinets | Device Description |
Residential distribution room | spaces | <10m² | OLT Sinking machine room | 300A Power Supply System | 1+1 | Rated load: 5.8kw Maximum load: 10.8kw Backup time: 3h Air conditioning capacity: 1P |
<10m² | CRAN+OLT Sinking machine room | 600A Power Supply System | 1+2 | Rated load: 8.6kw Maximum load: 21.6kw Backup time: 3h Air conditioning capacity: 2P | ||
10~20m² | CRAN+OLT Sinking machine room | 600A Power Supply System | 2+3 | Rated load: 14.3kw Maximum load: 21.6kw Backup time: 3h Air conditioning capacity: 4P | ||
Power supply station, substation, business station building | Independent room | 20~40m² | Node aggregation machine room | 600A Power Supply System | 2+3 | Rated load: 14.3kw Maximum load: 21.6kw Backup time: 3h Air conditioning capacity: 4P |
≥40m² | Core aggregation machine room | 1200A Power Supply System | 4 | Rated load: 28.8kw Maximum load: 43.2kw Backup time: 3h Air conditioning capacity: None (natural air cooling) |
- Professional power supply and distribution system: capable of providing stable AC to DC power output and sufficient backup working hours for power supply.
- Professional monitoring system: achieve centralized and platform based supervision, provide local supervision, and achieve real-time supervision on integrated cabinet door display screens and mobile phones. The system can obtain real-time monitoring data of the computer room infrastructure management system platform through the APP. This mainly includes real-time monitoring data of devices, alarm viewing and statistics, PUE energy consumption data, video image viewing, access control status management, etc.
- Professional temperature control system: The equipment cabinet is equipped with 4.2kw precision air conditioning, which adopts a circulating design inside the cabinet to achieve front air outlet and rear air return, with an air volume of 700m ³/ h. Fully meet the heat dissipation requirements of 8 BBU devices in a single cabinet.
- Professional safety system: the power supply cabinet is equipped with power supply, and the Battery management system can check the power supply online in real time. The battery runs safely and stably. The power supply cabinet and equipment cabinet can be optionally equipped with a fire self extinguishing system to achieve fire safety management. Video surveillance can provide 24-hour online video security monitoring.
modelparameter | 600 Type | 1000 Type | |||
Single cabinet size | mm | 1000×600×2200(Depth * Width * Height) | 1000×600×2200(Depth * Width * Height) | ||
Cabinet combination | mm | Triple connection (power cabinet * 1 unit+equipment cabinet * 2 units) | Five units (power cabinet * 2 units+equipment cabinet * 3 units) | ||
cover an area | m² | 2 | 3 | ||
Installation method | △ | Ground | Ground | ||
Ambient Temperature | ℃ | -40 ~ +55 | -40 ~ +55 | ||
Equipment capacity | U | 66 | 99 | ||
Number of equipment installed | units | 8 sets of BBUs, 2 sets of transmission equipment, and 1 set of OLT | 15 sets of BBU+2 sets of transmission+1 set of OLT | ||
Applicable scenarios | - | Small CRAN machine room, capable of OLT sinking, equal to 20 square meters of conventional machine room | Large CRAN computer room, which can be used as a converged computer room, equivalent to a 30 square meter conventional computer room | ||
| Integrated device parameters | ||||
AC portion | Input and output terminals | AC input: AC380V, 4P/100A × 2-way (mains power and oil engine interlocking) | |||
AC lightning protection | B级 60KA | B级 60KA | |||
Battery configuration | pieces | 6* 48V 100AH batteries | 10* 48V 100AH batteries | ||
DC portion | DC configuration of power cabinet | 12*50AH Efficient rectifier module | 20*50AH Efficient rectifier module | ||
DC configuration of equipment cabinet | 2*160A DC distribution unit | 4*160A DC distribution unit | |||
output | 4*63A/1P,4*32A/1P | 4*63A/1P,4*32A/1P | |||
Dynamic environmental monitoring | hardware configuration | Monitoring host+11.6-inch LCD display screen | |||
function | Monitoring unit, power supply, battery, air conditioning, emergency cooling system monitoring, door magnet, water immersion sensor, smoke sensor, temperature and humidity sensor | ||||
Temperature control equipment | Emergency cooling system | Electric air valve+emergency fan | Electric air valve+emergency fan | ||
air-conditioning | 1.5 horsepower wall mounted air conditioning | One equipment cabinet equipped with one 4.2kw rack mounted precision air conditioner | |||
ODF | Optional | Optional according to equipment requirements (independent ODF rack can be used) | |||
Intelligent fire protection | Optional | The cabinet is equipped with an embedded heptafluoropropane fire extinguishing device (automatically activated when the temperature exceeds 68 ℃), which has no corrosion to electronic equipment and is non-toxic to the human body | |||
monitor | Optional | The cabinet is equipped with a built-in or external monitoring system, which cooperates with the dynamic loop system to complete real-time alarm monitoring |
1000 Type Cabinet
Equipment cabinet
600 Type Cabinet
Power cabinet
Battery cabinet
- High integration: Support integrated management and monitoring of power supply, energy storage, dynamic environment monitoring, equipment, and temperature control
- High reliability: High safety Lithium iron phosphate battery is used in combination with self-developed battery intelligent charge and discharge management system
- High reliability: The cabinet power supply is configured in N+2 mode, supporting oil engine interface
- Smart energy consumption: The high-efficiency rectifier module used in the AC/DC system has a rectification efficiency of over 97%
- Intelligent temperature control: The cabinet adopts precision rack type air conditioning, and the heating equipment has a complete closed air duct structure, which can achieve precise heat dissipation
- Smart monitoring: The system adopts a visual monitoring platform, implements a 7 * 24-hour duty system, and has voice and SMS alarm reminder functions
- Real time supervision: The system can obtain real-time monitoring data of the computer room infrastructure management system platform through the APP
- Warning function: Early warning, such as insufficient cold night air conditioning, power failure, and insufficient battery capacity, the system notifies maintenance personnel
- Intelligent fire fighting: the cabinet is equipped with fire fighting module, which can cooperate with smoke sensing and temperature sensing starting equipment to Automatic fire suppression